| Telecom Base Station Energy System Parameters | |||
| Model | HJ-CHI-18030-W | HJ-CHI-36040-W | |
| Cabinet | Dimensions | 1600mm*600mm*600mm | 2200mm*700mm*700mm |
| Application | Indoor floor-standing | Indoor floor-standing | |
| Weight | ≤95KG(excluding battery) | ≤145KG(excluding battery) | |
| Input | AC Input | AC 380V/220V、50Hz, MCB 63A/4P, SPD*1, output 16A*1 (optional) | AC 380V/220V、50Hz, MCB 63A/4P, SPD*1, output 16A*1 (optional) |
| PV/Wind Input | Supported, optional | Supported, optional | |
| Max Power | Capacity | 18KW(300A) | 36KW(600A) |
| Efficiency | 93%(optional 96%) | 93%(optional 96%) | |
| Rectifier | Single Module | 48V/ 50A module , optional 75A | 48V/ 50A module , optional 75A |
| Total Capacity | Max 18KW(300A), | Max 36KW(600A), | |
| Note: rectifier and PV share 300A total; full rectifier config leaves no PV capacity | Note: rectifier and PV share 300A total; full rectifier config leaves no PV capacity | ||
| PV Controller (MPPT) | Single Module | 48V/ 50A module , optional 75A | 48V, 50A/75A optional |
| MPPT Input Voltage | 60~150V, optional(200V~400V) | 60~150V, optional(200V~400V) | |
| Total Capacity | Max 18KW(300A), | Max 36KW(600A), | |
| PV Modules | Max PV Power (W) | Recommended 9KW, (3KW~18KW optional) | Recommended 18KW, (3KW~36KW optional) |
| Battery | Rated Voltage (V) | 48V(40~60V) | 48V(40~60V) |
| Max Charge/Discharge Current (A) | 90A (C-rate 0.3C) | 180A (C-rate 0.3C) | |
| Capacity | 30KWh | 40KWh | |
| Output | Bypass AC Output | 220/230Vac(380/400Vac) | 220/230Vac(380/400Vac) |
| DC48V Output Voltage | 43.2V DC ~58V DC(default 53.5V DC ) | 43.2V DC ~58V DC(default 53.5V DC ) | |
| Rated Output Power | Max 18KW(300A), | Max 36KW(600A), | |
| Peak Efficiency | 96% | 96% | |
| DC Output Interface | MCB: 125A*2、63A*2、32A*216A*2(user-configurable) | MCB: 125A*2、63A*2、32A*216A*2(user-configurable) | |
| Application | / | Grid-tied/off-grid 、Off-grid(OPTIONS) | Grid-tied/off-grid 、Off-grid(OPTIONS) |
Note: Specifications shown are standard values. Actual performance may vary depending on installation environment, component compatibility, and grid conditions. We reserve the right to continuously optimize design and specifications. For final technical proposals and formal quotations, please contact our sales team to request an official specification confirmation document.